Ver.
Smart MBS RRH-P4 Installation Manual/Ver.3.0
© SAMSUNG Electronics Co., Ltd.
2-45
2600-00CTEIGAA
4.0
Installing the Circuit Breaker
To ensure stability in power supply, a circuit breaker must be installed on the
power cable connected to the rectifier (or power distributor).
Capacity of -48 VDC circuit breaker is 32 A.
Pressure terminal
As for the pressure terminal or the cable, the UL Listed products or equivalent
should be used.
Ex) RRH-P4 AWG8 (6 mm
2
)Type
: Manufacturer-Spec-Kon, Part No: K8-10R-D