5. Parameters
5-53
5.7.3.3 Adjusting analog inputs : H2.03, H2.04, H2.06, H2.07
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
H2.03
Voltage Input
Gain
(Terminal 9)
0.1%
0.0
~200.0
100.0 O
H2.04
Voltage Input
Bias
(Terminal 9)
0.1%
-100.0
~100.0
0.0 O
H2.06
Current Input
Gain
(Terminal 10)
0.1%
0.0
~200.0
100.0 O
H2.07
Current Input
Bias
(Terminal 10)
0.1%
-100.0
~100.0
0.0 O
• Adjust gain and bias of analog inputs, as shown in Figure 5.22 if there
are undesirable offset and gain changes in the analog inputs.
• The setting unit of gain and bias changes according to the values in
H2.05. For more details, see the paragraph 5.7.3.4.
Figure 5.22 Gain and Bias
Analog input
Max. Output Frequency
x
Gain
100
Max. Output Frequency
x
Bias
100
0V
(4mA)
10V
(20mA)
Use the current value in parenthesis
when current input has been selected
When H2.05=0
Frequency
Command
5-54
MOSCON-E7 User’s Manual
5.7.3.4 Setting the multi-function analog input terminal
function : H2.05
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
H2.05
Function of
Current
Input Terminal
- 0~
7 0
X
• H2.05 is used to set the function of Ain(no. 10) terminal.
• Constants and function for multi-function analog input
• Setting
Setting
constant
Function
Setting unit is the percentage of
0
Frequency command
Max. output frequency
1
Frequency gain
Max. output frequency
2
Voltage bias
Max. output voltage
3
DC breaking current
Max. output current
4
Over torque detection level
Max. output current
5
Stall prevention level during
operation
Max. output current
6
Minimum frequency command
level
Max. output frequency
7
Jump frequency
Max. output frequency