5. Parameters
5-29
5.5.6 Automatic torque boost
MOSCON-E7 automatically adjust the output torque by detecting the
variation in a load, to provide better speed control performance.
5.5.6.1 Torque compensation gain : S5.01
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
S5.01
Torque
Compensation Gain
1% 0~250
100
X
• Normally adjustment of S5.01 is not required.
• Raise the value in S5.01 if the output wiring between inverter and
motor is long, or when the capacity of installed motor is quite smaller
than the maximum motor capacity of the inverter.
• Decrease the value in S5.01, if the excessive mechanical vibration
occurs.
5.5.6.2 Torque compensation delay : S5.02
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
S5.02
Torque
Compensation
Delay Time
1msec 0
~9999
20
X
• Normally adjustment of S5.02 is not required.
• Raise the value in S5.02 if the mechanical vibration occurs.
• Decrease the value in S5.02 if the performance of speed regulation is
poor.
5-30
MOSCON-E7 User’s Manual
5.5.7 System function compensation
5.5.7.1 Hunting prevention gain : S6.01/S6.03
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
S6.01
Hunting
Prevention Gain
% 0~100
20
O
S6.03
Current ripple
restraint
(1 phase only)
- 0~1 1
X
• Normally adjustment of S6.01 is not required.
• Raise the value in S6.01 if mechanical vibration occurs under a light
load condition.
• Decrease the value in S6.01 if stall occurs.
• S6.03 is used in restraining from the unique current ripple in 1 phase
only(Invalidness in 3 phase).
5.5.7.2 Boosting brake performance : S6.02
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
S6.02
Enable
Brake Boosting
-
0 ~ 1
0
X
• If S6.02=1, the performance of braking is increased. However, since
frequent braking under this condition may damage the inverter, use this
function carefully.