5. Parameters
5-35
V/f pattern: 2.2~3.7kW
Figure 5.13.1 V/f pattern: settings 0~14 & setting15
(For 400V class, doubles the voltage in Figure)
Setting
0
50Hz
Setting
1
60Hz
(V)
(V)
200
200
14
14
8
8
(Hz)
(Hz)
0
0
1.3
1.5
2.5
3
50
60
Setting
2
60Hz
(V)
200
14
8
(Hz)
0 1.5 3
50 60
Setting
3
72Hz
(V)
200
14
8
0 1.5 3
60
72
Setting
4
50Hz
(V)
200
35
6
(Hz)
0 1.3
25
50
Setting
5
50Hz
(V)
200
50
7
(Hz)
0 1.3
25
50
Setting
6
60Hz
(V)
200
35
6
(Hz)
0
1.5
30
60
Setting
7
60Hz
(V)
200
50
7
(Hz)
0 1.5
30
60
5-36
MOSCON-E7 User’s Manual
Figure 5.13.2 V/f pattern : settings 0~14 & setting15
(For 400V class, doubles the voltage in Figure)
Setting
8
50Hz
(V)
200
18
9
(Hz)
0 1.3 2.5
50
Setting
9
50Hz
(V)
200
23
11
(Hz)
0 1.3 2.5
50
Setting
10
60Hz
(V)
200
18
9
(Hz)
0 1.5 3
60
Setting
11
60Hz
(V)
200
23
13
(Hz)
0 1.5 3
60
Setting
12
90Hz
(V)
200
14
7
(Hz)
0 1.5 3
60 90
Setting
13
120Hz
(V)
200
14
7
(Hz)
0 1.5 3
60 120
Setting
14
180Hz
(V)
200
14
7
(Hz)
0 1.5 3
60 180