5. Parameters
5-15
5.4 F-Parameter
5.4.1 Frequency control functions
5.4.1.1 Setting the frequency/speed command : F0.01~F0.09
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
F0.01
Main frequency
command of
operator mode &
communication
mode
0.01Hz
0.00
~600.00
0.00 O
F0.02
~F0.08
Frequency 2~8
0.01Hz
0.00
~600.00
0.00 O
F0.09 Jog
Frequency
0.01Hz
0.00
~ 600.00
6.00 O
• Parameters F0.01~F0.09 are frequency commands used for multi-step
speed operation as shown in Fig 5.3.
• In multi-step speed operation, JOG command has the top priority.
Thus, when JOG command is on, the frequency command is changed
to F0.09 regardless of terminal status of multi-step speed reference 1~3.
• In keypad mode (B0.01=1) and communication mode (B0.01=3), the
value in F0.01 becomes the active frequency command.
Figure 5.3 Timing chart for multi-step and JOG operation
RUN/STOP
F0.09
Reference 2
Auxiliary speed
Reference 1
F0.08
F0.07
F0.06
F0.05
F0.04
F0.03
F0.02
F0.01
Reference 3
Reference 4
Reference 5
Reference 6
Reference 7
Reference 8
JOG frequency
Frequency
reference
Multi-step speed reference 1
Multi-step speed reference 2
Multi-step speed reference 3
JOG reference
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
5-16
MOSCON-E7 User’s Manual
5.4.2 Frequency limit
5.4.2.1 Setting lower/upper frequency limit : F1.01,F1.02
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
F1.01
High Speed Limit 0.1%
0.1~100.0
100.0
O
F1.02 Low
Speed
Limit
0.1%
0~99.9 0.0
O
• Parameter F1.01 and F2.02 are used to set the upper and lower limit of
output frequency respectively.
• The setting unit of F1.01 and F1.02 is the percentage of the maximum
utput frequency (C0.02).
Figure 5.4 Upper and lower limits of the frequency reference
5.4.3 Jump frequency to avoid mechanical
resonant oscillation
5.4.3.1 Setting jump frequency : F1.03~F1.06
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
F1.03 Jump
Frequency1
0.01Hz
0.00
~600.00
0.00 O
F1.04 Jump
Frequency2
0.01Hz
0.00
~600.00
0.00 O
F1.05 Jump
Frequency3
0.01Hz
0.00
~600.00
0.00 O
F1.06
Jump Frequency
Width
0.01Hz
0.00
~20.00
0.50 O
Internal Frequency Reference
Frequency Reference
Upper Limit (F1.01)
Frequency Reference
Lower Limit (F1.02)
Frequency Command
from User