Appendix A-1
Appendix A
Factory setting that change with the motor capacity
C2.01
Motor
terminal
resistance
(
Ω
)
C2.02
Motor
iron
loss
(Watt)
C2.03
Motor
rated
current
(A)
C2.04
Motor
no load
current
(A)
C2.05
Motor
rated
slip
(Hz)
20P4 10.50 25
2.40 1.40 3.83
20P7 7.50 30 3.80 2.20 3.66
21P5 2.60 75 6.60 4.30 3.00
22P2 1.80 90 9.00 4.40 2.67
23P7 0.90 200 14.30 7.00 2.33
40P4 26.00 30
1.40 0.90 3.83
40P7 18.00 45
2.20 1.30 3.66
41P5 9.70 83 3.80 2.20 3.00
42P2 4.60 150 5.20 2.50 2.67
43P7 3.00 230 8.30 4.00 2.33
A-2
MOSCON-E7 User’s Manual
Appendix B
Monitors
Name
Unit
Display
Page
U0.01 Effective
Frequency
Command
0.01Hz xx.xx~xxx.x 5-4
U0.02 Current
Output
Frequency
0.01Hz xx.xx~xxx.x 5-4
U0.03
Output Current in RMS
0.01A
xx.xA
5-4
U0.04
Output Voltage in RMS
1V
xxxu
5-4
U0.05
DC link Voltage
1V
dxxx
5-4
U0.06
Output Power in 0.1kW
0.1kW
Pxx.x
5-4
U0.07
Motor speed in RPM
1rpm
xxxx
5-4
U0.08 Percentage
Output
Torque
1%
oxxx 5-4
U0.09 I/O
Status
bit
5-4
U0.10
Cumulative Power On Time
10Hr
xxxx
5-4
U0.11
Elapsed Time since Power On
min.sec
mm.ss
5-4
U0.12 S/W
Version
r.xxx
5-4
Last Fault
Name
Unit
Display
Page
U1.01 Command
Frequency 0.01Hz
xx.xx~xxx.x
5-5
U1.02 Output
Frequency 0.01Hz
xx.xx~xxx.x
5-5
U1.03 Output
Current 0.01A
xx.xA
5-5
U1.04 Output
Voltage
1V xxxu
5-5
U1.05 DC
Voltage
1V
dxxx
5-5
U1.06 Output
Power 0.1kW
Pxx.x
5-5
U1.07 Motor
rpm 1rpm
xxxx
5-5
U1.08 Output
Torque
1% oxxx
5-5
U1.09 I/O
Status
bit
5-5
U1.10
Cumulative Power On Time
10Hr
xxxx
5-5
Fault List
Name
Unit
Display
Page
U2.01
Fault 1 (recent)
-
*
5-5
U2.02 Fault
2
- *
5-5
U2.03 Fault
3
- *
5-5
U2.04 Fault
4
- *
5-5