5. Parameters
5-55
5.7.4 Multi-function analog output : H3.01~H3.03
5.7.4.1 Setting multi-function analog output : H3.01
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
H3.01
Analog Monitor
Function Setting
- 0~7 1
X
• H3.01 is used to select the function of the analog monitor output
terminal.
• Setting
Setting
constant
Function
Reference
0 Frequency
command
U0.01
1 Output
frequency
U0.02
2 Output
current
U0.03
3 Output
voltage
U0.04
4 DC
voltage
U0.05
5 Output
power
U0.06
6 Motor
speed
U0.07
7 Estimated
torque
U0.08
5-56
MOSCON-E7 User’s Manual
5.7.4.2 Adjusting the monitor output : H3.02, H3.03
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
H3.02
Analog Monitor
Gain setting
0.1%
0.0
~200.0
100.0 O
H3.03
Analog Monitor
Bias setting
0.1%
-100.0
~100.0
0.0 O
• H3.02 and H3.03 are used to set the gain and bias of monitor output.
• H3.02 : set what multiple of 10V will correspond to a 100% output of
the monitored item.
• H3.03: set the amount that the output characteristic will be shifted
vertically. Set this amount as a percentage, with 10V corresponding to
100%.
Figure 5.23 Monitor output adjustments
Analog output
Max. Output Frequency
x
Gain
100
Max. Output Frequency
x
Bias
100
0V
10V
Use the current value in parenthesis
when current input has been selected
When H3.01=0
Frequency
Command