5. Parameters
5-11
• Active source of RUN command in local and remote mode can be
selected independently as follows.
Digit1
Digit0
B0.02
Active source of RUN
command in local mode (0~1)
Active source of RUN command
in remote mode (0~2)
• Setting
Setting
constant
Reference source
0
Operator (RUN/STOP key on keypad)
1
Contact input (contact 1 or 2 on terminal block)
2 Communication
(RS-485)
5.3.1.3 Selecting stopping method : B0.03
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during operation
B0.03
Stopping
method
- 0~1 0
X
• B0.03 is used to select the stopping.
• Setting
Setting
constant
Function
0 Ramp
to
stop
1 Free
run
stop
5.3.1.4 Prohibiting the reverse rotation : B0.04
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
B0.04
Prohibiting
Reverse Rotation
- 0~1 0
X
• B0.04 is used to prohibit the reverse run
• Setting
Setting
constant
Function
0
Reverse rotation enabled
1 Reverse
rotation
disabled
5-12
MOSCON-E7 User’s Manual
5.3.1.5 Setting the motor direction : B0.05
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
B0.05
Default Motor
Direction
- 0~1 0
O
• B0.05 is used to select the direction of the motor’s rotation
• It is only applicable when B0.02 = 0 (operator)
• Setting
Setting
Function
0
Forward (CCW from the axis view)
1
Reverse (CW from the axis view)
• If B0.04=1, it is automatically changed to 0(forward).
5.3.1.6 Setting the monitor default : B0.06
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during
operation
B0.06
Default Monitor
Item
- 1~10 0
O
• B0.06 is used to sets the monitor item to be displayed when the power
is turned on.
• If B0.06=5, U0.05 is displayed at power-up.
5.3.1.7 Setting the automatic start operation : B0.07
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during operation
B0.07
Automatic start
after power on
- 0~1 0
O
• B0.07 is set to 1, if the motor is to be started automatically at power-up.
• The automatic start option (B0.07=1) is valid only when the active
source of run command is the digital operator. (B0.02=0)
• Setting
Setting
constant
Function
0
Does not use the automatic start operation.
1
Motor runs automatically without RUN command.