EB 5573 EN
Error during operation
9 Error during operation
The
icon blinks on the display when a sensor fails. Additionally, the display is illuminated
for one second every 10 seconds upon sensor failure. 'Error' is immediately indicated. Press
the rotary pushbutton to open the error level. Turn the rotary knob to read the error or possi-
bly more. As long as an malfunction exits, the error message is included in the reading loop,
even when it has not been opened by pressing the rotary pushbutton.
In the error level, the error message is displayed as specified in the following list (sec-
tion 9.1).
After the system code number has been changed or after restarting the controller, any error
messages are suppressed for approx. three minutes.
9.1 Error list
Err 1 = Sensor failure (see section 9.2)
Err 2 = Reserved
Err 3 = Disinfection temperature not reached (see section 7.10)
Err 4 = Max. charging temperature reached (see section 7.2)
Err 5 = Reserved
Err 6 = Temperature monitor alarm (see section 9.3)
Err 7 = Unauthorized access occurred
Err 8 = Error message of a binary input
All error messages, except for Err 1 can be confirmed in the error level.
Confirming error messages
1.
Select
Clr
[
q
].
2.
Confirm error message [
Û
].
Note