EB 5573 EN
15
Operation
6. Select period/day for which the times-of-use are to be
valid [
q
].
1-7 = daily
1 = Monday, 2 = Tuesday, …, 7 = Sunday
START
7. Activate editing mode for the period/day [
Û
].
Reading:
START
,
and
blink.
8.
Change start time [
q
].
The time is set in steps of 15 minutes.
STOP
9. Confirm the start time setting [
Û
].
Reading:
STOP
10.
Change stop time [
q
].
The time is set in steps of 15 minutes.
11.
Confirm the stop time setting [
Û
].
Reading:
START
The displayed time is the stop time of the first time-of-use
period plus 15 minutes.
Î
To set the second and third times-of-use periods, repeat steps 8 to 11.
Î
If no further times-of-use are to be programmed for the selected time period/day, exit the
menu by confirming the indicated start time twice (2x [
Û
]).
Î
For programming every day separately, repeat steps 6 to 11.
12.
Once you have programmed all times-of-use: Turn the rotary switch back to normal
switch position (information level).
Do not use the 1–7 menu to check the programmed times-of-use. If this menu is opened after
the times-of-use have been programmed, the schedule programmed for Monday is also ad
-
opted for all other days of the week.
Note