EB 5573 EN
121
Appendix
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
20
Modbus
without
building
automation
system
0
All
CO6 > F20 - 1: Various Modbus specifications do not have
any effect on the collective level/building automation system
reading
F Function block number, WE Default setting, Anl System code number
CO8: Initialization of BI1 and BI2 (all systems)
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
01
Analysis of BI1
0
All
CO8 > F01 - 1: analysis active
Function block parameters:
Error message when BI = 0, BI = 1, none (1)
02
Analysis of BI2
0
All
CO8 > F02 - 1: analysis active
Function block parameters:
Error message when BI = 0, BI = 1, none (1)
13.2
Parameter lists
PA1: PA1 parameters (heating circuit 1)
PA2: PA2 parameters (heating circuit 2)
Display reading
Parameter name
Value range (default setting)
Flow gradient
0.2 to 3.2 (1.8)
(when CO1, 2 > F05 - 1, 0.2 to 1.0 (1.0) applies)