EB 5573 EN
19
Operation
We recommend deleting public holidays that are not assigned to a specific date by the end
of the year so that they are not carried on into the following year.
2.8.2
Entering vacations
The system runs constantly in reduced mode during vacation periods. A maximum of ten va-
cation periods can be entered. Each vacation period can be separately assigned to the heat-
ing circuits HC1, HC2 and/or the DHW circuit.
Parameters
WE
Level: value range
Vacation period (START, STOP)
–
Extended information level: 01.01 to 31.12
Proceed as follows:
1.
In the extended information level (normal switch position
) select the data point for vacations [
q
].
Reading:
2.
Open data point for public holidays [
Û
].
Reading:
START
3. Select
– –.– –
on the display [
q
] (if applicable).
4.
Activate editing mode for the start date of the vacation
[
Û
].
and
blink.
5. Set the start date of the vacation [
q
].
6. Confirm the start date setting [
Û
].
Reading:
STOP, – –.– –
7. Set the end date of the vacation [
q
].
8.
Confirm the end date setting [
Û
].
Black squares at the top of the display indicate the
assignment of the vacation periods to the individual
control circuits.
Note