Start-up
The modifications of the controller configuration and parameter settings described in this sec-
tion can only be performed after the valid key number has been entered.
The key number that is valid on the first start-up can be found on page 144. To avoid unau-
thorized use of the service key number, remove the page or make the key number unread-
able. In addition, it is possible to enter a new, customized key number (see section 8.19).
3.1
Setting the system code number
Different hydraulic schematics are available. Each system configuration is represented by a
system code number. The different schematics are dealt with in section 5. Available controller
functions are described in sections 6, 7 and 8.
Changing the system code number resets previously adjusted function blocks to their default
settings (WE). Function block parameters and parameter level settings remain unchanged.
The system code number is set in the configuration and parameter level.
Proceed as follows:
1.
Turn the rotary switch to (parameter and configuration level).
Reading:
0 0 0 0
2.
Enter valid key number [
q
]
3. Confirm key number [
Û
]
Reading:
PA_
4.
Select
Anl
on the display.
5. Activate editing mode for the system code number [
Û
]
blinks.
6. Select system code number [
q
]
7. Confirm system code number [
Û
]
Reading:
End
8.
Turn the rotary switch back to normal switch setting (information level).