35
value, loading pump will be enabled and the tank will be loaded
again.
➢
Legionella
OFF, ON
OFF
OFF
–
disables Legionella function,
ON
–
enables Legionella function.
Every week, at 2:00 a.m.
, hot tap water will be heated to 70°C in
order to disinfect the DHW tank. Note: risk of scalding form hot
water!
➢
Heat loss protection
OFF, ON
ON
Protection against reverse transfer of heat from the DHW tank to
heat source/buffer. The setting
OFF
disables the comparison of
temperature between the sensors H1-S and DHW.
System settings
Name
Range
Settings
Description
Main heat source
➢
Mode
ON, OFF
ON
OFF
–
controller does not affect heat source operation,
ON
–
controller enables or disables heat source acc. to a heat
demand.
➢
Hysteresis
1…30
4
°C
Heat source hysteresis. Heat source is activated when set water
temperature
–
Hysteresis/2. Heat source is deactivated at set
water tempe Hysteresis/2.
➢
Minimum
temperature
20…80
20°C
Minimum temperature of heat source and minimum temperature
of H1 circuit (nonadjustable).
➢
Maximum
temperature
20…80
20°C
Maximum temperature of heat source and maximum temperature
of H1 circuit (nonadjustable).
➢
Boiler
cooling
temperature
40…
100
95
°C
Excess heat will be transferred to the heating circuits and HUW
when the temperature exceeds
Boiler cooling temperature
.
➢
Temperature of
start pumps
1…80
50°C
The H2 and H3 pump will be enabled when DHW temperature
exceeds
Temperature of start pumps
parameter value.
➢
Increasing
preset
temperature
0…20
5°C
Increasing the preset temperature of heat source more than the
HUW tank or heating circuit.
Note: heat source preset temperature is also a H1 nonadjustable
circuit preset temperature.
➢
Pump operation
extension
0…20
5min
The pump boiler is extended after turning off the main source of
heat.
➢
Start delay
0…24
0h
The heat source moves after a delay. Intended for installation of
heat buffer loaded by the fireplace.
➢
Off by no heat
demand
OFF,ON
OFF
ON
- if the thermostat do not report need to heat - the main heat
source is turns off, even though the preset temperature in water
has not been reached.
OFF -
the heat source is turns off after reaching the preset
temperature of water.
Note: the main heat source turns on to the heating of DHW.
➢
Control mode
No modulation,
Modulation 5K,
Modulation 10K,
Modulation 20K
No
modulation
No modulation
- the main source of heat works without output
modulation.
Modulation 5K, Modulation 10K, Modulation 20K
- the main heat
source operates with 0-10V output modulated.
More information in point 9.11
Additional
heat
source
➢
Selection
OFF, ON
OFF
OFF
–
disables operation of additional heat source.
ON
–
the controller switches the additional heat source on or off
depending on the heat demand.
➢
Temp.
deactivation
of
main
heat
source
20…80
40°C
Heat source is deactivated when temperature exceeds this value
measured on additional heat source sensor.
➢
Pump
start
temperature
1…80
50°C
Fireplace pump will be enabled when fireplace or automatic boiler
temperature exceeds
Pump start temperature
parameter value.
➢
Boiler
cooling
temperature
70…100
92°C
Excess heat will be transferred to the heating circuits and DHW
when the temperature sensor of additional heat source exceeds
Boiler cooling temperature
.
Hydraulic scheme
1…8
1
Parameter defines characteristic features of the hydraulic system.
More information in point 11
Frost protection
mode
OFF, ON
OFF
OFF
–
disables frost protection mode.
ON
–
enables frost protection mode.
Frost
protection
delay time
1…12
4h
Delay time of activation the frost protection mode
Frost Protection
setpoint
temperature
3…25
7°C
Below this temperature frost protection mode is activated.