22
Hydraulic scheme no. 4 -
diagram “
B
” with heat buffer
4
:
1
–
boiler
2
–
boiler pump
3
–
buffer temperature sensor
4
–
heat buffer
5
–
fireplace pump controlled by fireplace regulator
6
–
temperaturę sensor
7
–
fireplace with water jacket
8
–
regulated circuit water temperature sensor (H2)
9
–
circuit pump (H2)
10
–
electrical servo of H2 regulated heat circuit
11
–
fireplace regulator
12
–
thermostatic valve protecting return temperature.
PROPOSED SETTINGS:
Parameter
Setting
MENU
Hydraulic diagram
4
menu
→
service settings
→
System
Selection
ON
menu
→
service settings
→
System
→
Additional heat source
Temperature deactivating main
heat source
35
C
menu
→
service settings
→
System
→
Additional heat source
Pump start temperature
55
C
menu
→
service settings
→
System
→
Additional heat source
Cooling temperature
92
C
menu
→
service settings
→
System
→
Additional heat source
Minimum temperature
25
C
menu
→
service settings
→
System
→
Main heat source
Description: Pump (2) works together with boiler (1). When boiler (1) switches off, pump (2) deactivates with 5 minute
delay. After fireplace sensor (6) is heated up to a temperature of (35
C), boiler (1) and pump (2) deactivates with 5
minute delay. Pump (5) is controlled by fireplace regulator (11). When (6) exceeds 92
C, heat excess will be transferred
to heat and HUW circuits. Pump (9) will switch off if temperature on sensor (3) drops below 25
C.
4
Shown hydraulic diagram does not replace a central heating system and can be used only for demonstrative purposes
!