All the cabinets and accessories must be earthed in accordance with the current standards.

3.- CONTROL PANEL.

3.1.- Introduction.

The control panel is in the frontal side of the UPS, which is used to monitor its general and battery status and the corresponding

alarms in a easy way.

That control panel is based in a LCD panel that shows the operating status, measurements and alarms, and by an E.P.O. button

located in the bottom-right side.

The LCD panel shows text messages and operating parameters in a LCD screen of 4 rows with 20 characters per each one.

The screens are organised in 7 multilevel menus , which can be selected by using the keys placed under the LCD panel.

In the left side of the LCD, there are two LEDs, one is green labelled as “NORMAL” and the other one is red labelled as “ALARM”.

The behaviour of both LED is summarized in the table 3.1a.

During the normal operating and to identify the UPS master, in case of parallel systems, the green LED blinks.

Tab 3.1a

STATUS

UPS OK

ACTIVE ALARM

DEACTIVE ALARM

GREEN LED

ON

OFF

ON

RED LED

OFF

ON

BLINKING

Key

ESC

Allow silenci the

acoustic alarm

Key

MENU

Allow escaping

from the selected

menu.

Figure 3-1b LCD panel composition

Key

BACK

Key

NEXT

Allow moving from one menu to another. If both

are pressed together is the

ENTER

function.

Содержание SLC ELITE MAX Series

Страница 1: ...User s and installation manual UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series from 160 to 300kVA EK449A01...

Страница 2: ...2...

Страница 3: ...3 SAFETY WARNINGS 6 User s manual installation and start up 4 39...

Страница 4: ...3 Operating principle 1 3 1 UPS block diagram 1 3 2 Input power module and output 1 3 3 Control and auxiliary circuits 1 3 4 Batteries 1 3 5 Manual bypass 1 3 6 Frontal panel 2 INSTALLATION STANDARDS...

Страница 5: ...ete UPS shutdown 4 8 Emergency Power Off E P O 4 9 Instructions to start up the UPS in ECONOMY mode 4 10 Instructions for transferring to manual bypass in ECONOMY mode 4 12 Instructions for complete U...

Страница 6: ...e conformity with the CEE Directives by means of the following harmonised standards EN IEC 62040 1 2 Uninterruptible Power Suppply UPS Part 1 1 General safety requirements for UPS used in accessible a...

Страница 7: ...1 1 2 Power and back up time Thanks to its modular configuration the power rates of this series are between 160 KVA and 300 KVA It is not foreseen any internal battery string so to achievethe wanted b...

Страница 8: ...e terminal strip M1 The system already has a remote communication card and a slot to place an optional one if it is requested for more information see chapter 2 7 Auxiliary connections of the UPS 1 2...

Страница 9: ...ICADOR CONVERTIDOR STEP UP RECTIFIER STEP UP CONVERTER INVERSOR INVERTER INTERRUPTOR EST TICO STATIC SWITCH SALIDA CARGA OUTPUT LOAD CARGADOR DE BATER AS BATTERY CHARGER ARMARIO DE BATER AS BATTERY CA...

Страница 10: ...S immediately respectively The communication interface can control a part from the standard relay card an additional one which is optional The auxiliary power supply feds all the PCB s and electronic...

Страница 11: ...from high humidity and heat sources from 5 to 40 C non condensing humidity lower than 95 When the battery cabinet isalsosupplied it is amust to assure that the period timebetweenthe last recharge oft...

Страница 12: ...SIONS D x W x K 160 720 200 720 250 870 300 870 DIMENSIONS D x W x K 160 780 200 780 250 990 300 990 SIX PHASE VERSION 800 x 1240 x 1800 POWER kVA WEIGHT Kg THREE PHASE VERSION 800 x 1240 x 1800 SIX P...

Страница 13: ...l the cables enter through the bottom window as it is showed in the figure 2 4 side view 2 5 Location features The UPS installation site must be clean and with a contamination degree of 2 IEC also it...

Страница 14: ...urrent higher than 500mA delayed and ready to support loads with DC component RCD type B Diagram 2 6a Bypassestandar Standard bypass Carga Load Red principal Standardmains BYPASSDE MANTENIMIENTO MAINT...

Страница 15: ...RNALLY TO THE UPS AT THE MAINS INPUT A CONTACTOR A PART FROM THE PROTECTION CIRCUIT BREAKER IN ORDER TO PROTECT AGAINST BACKFEED VOLTAGES IN ACCORD ANCE WITH THE TABLE 2 6 AND THE FOLLOWING CIRCUIT DI...

Страница 16: ...ed in the internal side of the UPS door KVA Their features must inaccordancewith the IEC standards or with the local regulations forcircuit breakers withcharacteristic C Theconnections must done in ac...

Страница 17: ...d This card allows the connection of the UPS with several external devices The card has a terminal strip with dry contacts M1 where it can connected the following a remote panel chapter 2 7 2 acoustic...

Страница 18: ...through the key 5 LED description 1 UPS ON green led Turned ON means the correct operation of the UPS turned OFF means that thereis oneormore alarms intheinverterstage acousticalarmon 2 ON BATTERY yel...

Страница 19: ...n and using see its corresponding manual 2 7 4 Remote E P O button Pay special attention to the connection of the buttons for the E P O function emergency power off That connection is based on several...

Страница 20: ...ection Theinput earthcablemust be connected tothe earth stud of the UPS That cablemust be thefirstone to be connected It isbetter to place an anti rust between the earth stud and the contact board to...

Страница 21: ...er each one The screens are organised in 7 multilevel menus which can be selected by using the keys placed under the LCD panel In the left side of the LCD there are two LEDs one is green labelled as N...

Страница 22: ...ed In this moment the user can decide to continue with the guided procedure by following the proposed visual indications till the system is completed started up or to execute different operations thro...

Страница 23: ...ING CORRECT MAINS OUT OF RANGE The input mains is present but the voltage is out of the specified range CORRECT BYPASS LINE OUT OF RANGE The bypass line mains is present but the voltage is out of the...

Страница 24: ...are still supplied STA TIC SW ITCH BLOCKED A fter 3 frustrated autom atic attem pts from bypass to inverter the U PS blocks the static sw itch in the bypass line position BA TTERY FAU LT BA TTERY TES...

Страница 25: ...F 3 3 LOAD TRANSFERRED TO INVERTER With this message when the key ENTER is pressed the load is transferred from bypass to inverter 3 4 LOAD TRANSFERRED TO BYPASS With this message when the key ENTER i...

Страница 26: ...e log list by pressing MENU the LCD panel will come back to the MAIN MENU To delete all the events and alarms the submenu DELETE DATA LOGGER must be selected and after that press ENTER After 3 minutes...

Страница 27: ...unning and uses the batteries to fed the loads because there is a mains failure This operating mode guarantees the non interrupted power supply of the loads till the end of autonomy 4 2 Power switches...

Страница 28: ...res If this menu is selected the following operations can be done UPS start up UPS shutdown Manual bypass activation I1 INPUT MAINS SWITCH I4 OUTPUT UPS SWITCH I2 INPUT BYPASS SWITCH I3 MANUAL BYPASS...

Страница 29: ...are checked we will proceed to start up the system as follows 1 Turn on the BYPASS MAINS SWITCH RESERVE I2 The LCD panel and the control of the UPS starts to run to disable the guided procedures which...

Страница 30: ...lect Inverter OFF and press ENTER By doing it the inverter is shutdown and the non interrupted power supply to the loads is not guaranteed 3 Turn on the MANUAL BYPASS I3 Remove the padlock or any othe...

Страница 31: ...nverter By means of the menu 3 UPS COMMANDS select the Inverter ON and press ENTER 6 Check the transfer from bypass line to inverter Wait for 30 seconds after that the static switch will do the automa...

Страница 32: ...d BE SURE THAT THE PHASE ROTATION OF THE INPUT AND BYPASS MAINS ARE CORRECT See fig 4 3 to know the meaning of each switch Once the above steps are checked the system can be started up in Economy mode...

Страница 33: ...perpart of theUPS 4 10 Instructions for transferring to manual bypass in ECONOMY mode If for any maintenance or other reasons the power supply of the critical loads must be done from the mains directl...

Страница 34: ...seconds after that the rectifier will start up with a walk in time in order to pre charge the internal capacitors avoiding any overcurrent at the input mains The LCD will show the message INVERTER SH...

Страница 35: ...educe the DC output voltage of the converter till the threshold when the battery discharge starts if it is correct at 2 V cell it will start to supply current Otherwise there will be displayed an alar...

Страница 36: ...allows checking all the operations during the installation and maintenance periods of each equipment Thegeneral manual bypassallowsisolating the complete systemwithno interruption inthefeeding of thel...

Страница 37: ...ON INVERTER SHUTDOWN Initial start up Start up the inverter Permanent overload Check the output OVERLOAD Continuous overload at the UPS output Check the load at the UPS output and the start up the inv...

Страница 38: ...ust be done by the UPS dealer company or by a specialised company recommended by the dealer company 7 1 Yearly maintenance or half yearly in some critical cases The yearly maintenance has the followin...

Страница 39: ...39...

Страница 40: ...40 08460Palautordera Tel 3493 8482400 sat salicru com salicru com...

Отзывы: