After 3 minutes of inoperation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.
3.4.- Menu 3: UPS controls.
By means of this menu we can give orders to the UPS.
After 3 minutes of no operation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.
3.5.- Menu 4: Guided procedures.
After 3 minutes of no operation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.
3.6.- Menu 5: Panel configuration.
MESSAGE
MEANING
4,1 UPS START UP
The user is guided to start up the equipment.
4,2 UPS SHUTDOWN
The user is guided to shutdown the equipment.
4,3 MANUAL BYPASS ACTIVATION
The user is guided to shutdown the UPS and bypass line. The loads are still fed with
no interruption through the manual bypass.
4,4 MANUAL BYPASS DEACTIVATION
The user is guided to restart up the UPS , the loads are still fed with no interruption
from the manual bypass.
MESSAGE
MEANING
3,1 INVERTER ON
3,2 INVERTER OFF
3,3 LOAD TRANSFERRED TO INVERTER
With this message, when the key ENTER is pressed, the load is transferred from
bypass to inverter.
3,4 LOAD TRANSFERRED TO BYPASS
With this message, when the key ENTER is pressed, the load is transferred from
inverter to bypass.
3,5 BATTERY TEST START
With this message, when the key ENTER is pressed, an automatic battery test will
start, which will take 30 seconds.
With this message, when the key ENTER is pressed, the user can start up or
shutdown the inverter in a permanent way. It is needed for starting up the inverter
and after a shutdown due to a permanent overload.
MESSAGE
MEANING
5,1 Date setting
Allow setting the current date by using the arrows to increase or decrease the
numbers.
5,2 Time setting
Allow setting the current time by using the arrows to increase or decrease the
numbers.
5,3 Battery test setting
Allow setting the automatic battery test by choosing the weekday, the number of
week between one test and the next one, and the time in the day when it must be
done.
5,4 Language setting
Allow choosing the language among: Spanish, English, French, German and Italian