- 14 -
If the installation has battery cabinet too, the location must guarantee a cooling equal or higher than the one stated in the table 2.5b
Likewise, remind that the average lifetime of the batteries is related with their operating temperature, the recommended one is
around 20°C.
(In case the 20º C are overcame, per each 10°C over, the “battery lifetime” is reduced in 50%.)
2.6.- Predisposition and mains connection.
To make the connection to the mains, it is recommended a solution like the one stated in the diagram 2.6a. The switches B-C-D
are circuit breakers without earth leakage protection or, in case it is needed, with a leakage current higher than 500mA, delayed
and ready to support loads with DC component (RCD type B).
Diagram 2.6a
Bypass estandar
Standard bypass
Carga /
Load
Red principal
Standard mains
BYPASS DE
MANTENIMIENTO
MAINTENANCE
BYPASS
P
A
NE
L
DE
D
IS
TRIBUCIÓN /
DIS
TRIBUT
IO
N
Red principal
Standard mains
Bypass estandar
Standard bypass
BYPASS DE MANTENIMIENTO
MAINTENANCE BYPASS
BYPASS
LÍNEA DE BYPASS
BYPASS LINE
ENTRADA
INPUT
SALIDA
OUTPUT
BATERÍA 1 /
BATTERY 1
ARMARIO DE BATERÍAS /
BATTERY CABINET
SAI
UPS
Tab.2.5b
Spare air for 15
Spare air for 30
Spare air for 1
minutes (m³/h)
hour (m³/h)
minutes (m³/h)
10
19
32
13
26
42
16
32
52
19
39
62
Spare air fot the hydrogen of the batteries
Tab.2.5a
H e at lo s s e s w ith
H e at lo s s e s w ith o u t
e x ch an g e
e xch an g e
1 6 0
8 ,2
3 ,5
2 0 0
9 ,9
4 ,1
2 5 0
1 2 ,8
5 ,3
3 0 0
1 5 ,5
6 ,5
P O W ER
N o m . P o w e r