Function Parameters
63 - 104
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
5
: 38400BPS
Note:
The baud rate between the upper monitor and the inverter
must be the same. Otherwise, the communication is not applied.
The bigger the baud rate, the quicker the communication speed.
P14.02
Digital bit
checkout
setting
The data format between the upper monitor and the inverter must
be the same. Otherwise, the communication is not applied.
0
: No check (N,8,1) for RTU
1
: Even check (E,8,1) for RTU
2
: Odd check (O,8,1) for RTU
3
: No check (N,8,2) for RTU
4
: Even check (E,8,2) for RTU
5
: Odd check(O,8,2) for RTU
1
○
P14.03
Communication
answer delay
0~200ms
It means the interval time between the interval time when the drive receive
the data and send it to the upper monitor. If the answer delay is shorter than
the system processing time, then the answer delay time is the system
processing time. If the answer delay is longer than the system processing
time, then after the system deal with the data, waits until achieving the
answer delay time to send the data to the upper monitor.
5
○
P14.04
Communication
overtime fault
time
0.0 (invalid), 0.1~60.0s
When the function code is set as 0.0, the communication overtime
parameter is invalid. When the function code is set as non-zero, if the
interval time between two communications exceeds the communication
overtime, the system will report “RS485 communication faults” (CE).
Generally, set it as invalid; set the parameter in the continuous
communication to monitor the communication state.
0.0s
○
P14.05
Transmission
fault
processing
0
: Alarm and stop freely
1
: No alarm and continue to run
2
: No alarm and stop according to the stop means (only
under the communication control)
3
: No alarm and stop according to the stop means (under all
control modes)
0
○