Function Parameters
57 - 104
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P09.09
Output upper
limit of PID
These parameters are used to set the upper and lower limit
of the PID adjustor output.
100.0 % corresponds to Max. Frequency
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
100.0%
○
P09.10
Output lower
limit of PID
0.0%
○
P09.11
Feedback
offline
detection value
Set the PID feedback offline detection value when the
detection value is smaller than or equal to the feedback
offline detection value, and the lasting time exceeds the set
value in P09.12, the inverter will report “PID feedback offline
fault” and the keypad will display PIDE.
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
0.0%
○
P09.12
Feedback
offline
detection time
1.0s
○
P09.13
PID adjustment
selection
0x00~0x11
LED ones
:
0
:
Keep on integral adjustment
when the frequency achieves the
upper and low limit; the integration shows the change between the
reference and the feedback unless it reaches the internal integral
limit. When the trend between the reference and the feedback
changes, it needs more time to offset the impact of continuous
working and the integration will change with the trend.
1
:
Stop integral adjustment
when the frequency reaches the upper and low
limit. If the integration keeps stable, and the trend between the reference and the
feedback changes, the integration will change with the trend quickly.
LED tens
:
0
:
Same to the setting direction
; if the output of PID
adjustment is different from the current running direction, the
internal control will output 0 forcedly.
1
:
Opposite to the setting direction
0x00
○