Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P11.03
Overvoltage
stall protection
0
:Disabled
1
:Enabled
1
○
P11.04
Overvoltage
stall point
120~150%
120%
○
P11.05
Current limit
action selection
The actual increasing ratio is less than the ratio of output frequency
because of the big load during ACC running. It is necessary to take
measures to avoid overcurrent fault and the inverter trips.
During the running of the inverter, this function will detect the output
current and compare it with the limit level defined in P11.06. If it
exceeds the level, the inverter will run at stable frequency in ACC
running, or the inverter will derate to run during the constant running.
If it exceeds the level continuously, the output frequency will keep on
decreasing to the lower limit. If the output current is detected to be
lower than the limit level, the inverter will accelerate to run.
Setting range of P11.05:
0
: current limit invalid
1
: current limit valid
Setting range of P11.06:50.0~200.0%
Setting range of P11.07:0.00~50.00Hz/s
1
◎
P11.06
Automatic
current limit
level
160.0%
◎
P11.07
Decreasing
ratio during
current limit
10.00Hz/s
◎