Function Parameters
39 - 104
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Note
: for the 2-wire running mode, when FWD/REV terminal is
valid, the inverter stops because of the stopping command from
other sources, even the control terminal FWD/REV keeps valid;
the inverter won’t work when the stopping command is canceled.
Only when FWD/REV is relaunched, the inverter can start again.
P05.14
S1 terminal
switching on
delay time
The function code defines the corresponding delay time of
electrical level of the programmable terminals from switching
on to switching off.
Setting range:0.000~50.000s
0.000s
○
P05.15
S1 terminal
switching off
delay time
0.000s
○
P05.16
S2 terminal
switching on
delay time
0.000s
○
P05.17
S2 terminal
switching off
delay time
0.000s
○
P05.18
S3 terminal
switching on
delay time
0.000s
○
P05.19
S3 terminal
switching off
delay time
0.000s
○
P05.20
S4 terminal
switching on
delay time
0.000s
○
P05.21
S4 terminal
switching off
delay time
0.000s
○
P05.22
S5 terminal
switching on
delay time
0.000s
○
P05.23
S5 terminal
switching off
delay time
0.000s
○