Function Parameters
45 - 104
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
BIT10
: input terminals state
BIT11
: output terminals state
BIT12
: torque set value(% on)
BIT13
: pulse counter value
BIT14
: length value
BIT15
: current stage in multi-step speed
Example
- Default Value: 0000 0011 1111 1111
P07.06
Displayed
parameters 2
of running state
0x0000~0xFFFF
BIT0
: analog AI1 value (V on)
BIT1
: analog AI2 value (V on)
BIT4
: motor overload percentage (% on)
BIT5
: the inverter overload percentage (% on)
BIT6
: ramp frequency given value(Hz on)
BIT7
: linear speed
0x0000
P07.07
The parameter
selection of the
stop state
0x0000~0xFFFF
BIT0
: set frequency(Hz on, frequency flickering slowly)
BIT1
: bus voltage (V on)
BIT2
: input terminals state
BIT3
: output terminals state
BIT4
: PID reference (% flickering)
BIT5
: PID feedback value(% on)
BIT7
: analog AI1 value (V on)
BIT8
: analog AI2 value (V on)
BIT11
: current stage in multi-step speed
BIT12
: pulse counters
Example
- Default Value: 0000 0000 1111 1111
0x00FF
○
P07.08
Frequency
display
coefficient
0.01~10.00
Displayed frequency=running frequency* P07.08
1.00
○
P07.09
Speed display
coefficient
0.1~999.9%
Mechanical rotation speed =120*displayed running
frequency×P07.09/motor pole pairs
100.0%
○
P07.10
Linear speed
displayed
coefficient
0.1~999.9%
Linear speed= Mechanical rotation speed×P07.10
1.0%
○