Keypad Operation Procedure
19 - 104
No.
Name
Description
3
Code
displaying
zone
5-figure LED display displays various monitoring data and alarm code such as set
frequency and output frequency.
4
Digital
potentiometer
Corresponds to AI1.
5 Buttons
Programming
key
Enter or escape from the first level menu and
remove the parameter quickly
Entry key
Enter the menu step-by-step
Confirm parameters
UP key
Increase data or function code progressively
DOWN key
Decrease data or function code progressively
Right-shift key
Move right to select the displaying parameter
circularly in stopping and running mode.
Select the parameter modifying digit during the
parameter modification
Run key
This key is used to operate on the inverter in key
operation mode
Stop/
Reset key
This key is used to stop in running state and it is
limited by function code P07.04
This key is used to reset all control modes in the
fault alarm state
Quick key
The function of this key is confirmed by function
code P07.02.
4.1 Keypad displaying
The keypad displaying state of CV10 inverters is divided into stopping state parameter, running state parameter,
function code parameter editing state and fault alarm state and so on.
4.1.1 Displayed state of stopping parameter
When the inverter is in the stopping state, the keypad will display stopping parameters which is shown in figure
4-2.
In the stopping state, various kinds of parameters can be displayed. Select the parameters to be displayed or
not by P07.07. See the instructions of P07.07 for the detailed definition of each bit.
In the stopping state, there are 14 stopping parameters can be selected to be displayed or not. They are: set
frequency, bus voltage, input terminals state, output terminals state, PID reference, PID feedback, AI1, AI2 and
the current stage of multi-step speeds, pulse counting value. P07.07 can select the parameter to be displayed
or not by bit and
》
/SHIFT can shift the parameters form left to right, QUICK/JOG (P07.02=2) can shift the
parameters from right to left.