42 - 104
Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P06.10
RO switching
on delay time
The function code defines the corresponding delay time of
the electrical level change during the programmable terminal
switching on and off.
The setting range :0.000~50.000s
0.000s
○
P06.11
RO switching
off delay time
0.000s
○
P06.14
AO output
0
: Running frequency
1
: Set frequency
2
: Ramp reference frequency
3
: Running rotation speed
4
: Output current (relative to twice the inverter rated current)
5
: Output current (relative to twice the motor rated current)
6
: Output voltage
7
: Output power
8
: Set torque value
9
: Output torque
10
: Analog AI1 input value
11
: Analog AI2 input value
14
: MODBUS communication set value 1
15
: MODBUS communication set value 2
16
~
30
: Reserved
0
○
P06.17
Lower limit of
AO output
The above function codes define the relative relationship
between the output value and analog output. When the output
value exceeds the range of set maximum or minimum output, it
will count according to the low-limit or upper-limit output.
When the analog output is current output, 1mA equals to 0.5V.
In different cases, the corresponding analog output of 100%
of the output value is different.
0.0%
○
P06.18
Corresponding
AO output to
the lower limit
0.00V
○
P06.19
Upper limit of
AO output
100.0%
○
P06.20
Corresponding
AO output to
the upper limit
10.00V
○