Change during operation: N = impossible,
Y* = possible (enabled by using ), Y= possible (enabled by using
)
-57-
FUNC
DATA
PID control
(Feedback signal)
This function selects a PID control feedback signal.
0 Terminal 12
(0 to +10Vdc)
1
Terminal C1
(4 to 20mAdc)
2
Terminal 12
(+1 to +5Vdc)
PID control (P-gain)
This function sets a P-gain.
0. 0 1 to 1 0. 0 P-gain from 0.01 to 10.0 times (1 to 1000%) (in increment of 0.01 step)
PID control (I-gain)
This function sets an integral time.
0. 0 : No integration
0. 1 to 9 9 9 : Integral time 0.1 to 999s
(in 0.1s step for 99.9s or less, 1s step for 100s or more)
PID control (D-gain)
This function sets a derivative time.
0. 0 0 : No derivative
0. 0 1 to 1 0. 0 : Derivative time 0.01 to 10.0s (in 0.01s step)
PID control
(Feedback filter)
This function sets a filter time constant of PID feedback.
0. 0 to 6 0. 0 : Time constants 0.0 to 60.0s (in 0.1s step)
Factory
setting
Change during
operation
1
N
H21
H24
H25
H22
H23
Factory
setting
Change during
operation
0.01
Y
Factory
setting
Change during
operation
0.0s
Y
Factory
setting
Change during
operation
0.00s
Y
Factory
setting
Change during
operation
0.5s
Y