- 82 -
Item
Specifications
Remarks
Overload
•
Internal electronic thermal overload relay protects drive overload.
Overvoltage
•
Detect the excessive DC link circuit voltage to stop drive.
Overcurrent
•
Detect overcurrent due to overload on drive output side to protect drive
Incoming surge
•
Detect incoming surge voltage between AC power and the earth to protect
drive.
Undervoltage
•
Detect the DC link circuit undervoltage to stop drive
Overheating
•
Detects the cooling fan fault or abnormal temperature rise of drive to pro-
tect drive.
Short-circuit
•
Detect overcurrent due to short-circuit on drive output side to protect drive.
Ground fault
•
Detects overcorrect due to ground fault on drive output side to protect drive.
(Detect at starting)
Motor protection
•
Protect general-purpose motor with electronic thermal overload.
Input phase fail-
ure protection
(only for 3-phase
200V series)
•
The drive is protected against phase failure on the input side or over-current
due to inter-phase imbalance.
Stall prevention
•
Controls frequency to prevent OC trip in case of the output current exceeds
the limit value during acceleration.
•
Lowers the frequency to hold almost constant torque in case of the output
current exceeds the limit value during constant speed running.
•
Controls frequency to prevent OU trip in case of the DC link circuit voltage
exceeds the limit value during deceleration.
Retry
•
“Retry” function can be set for the protective functions OC1 to OC3 and
OU1 to OU3.(No. of times of retry: 5, waiting time: 0.5s fixed.
Dielectric
strength test
•
At 2000Vac for 1 min. between any main circuit terminals and
ground.(10mA or less)
Protection
Megger test
•
At 500Vdc megger test between any main circuit terminals and ground
(5M
Ω