-73-
8-3
Electrical measurements in the Main Circuit
The indicated values depend on the meter types because of harmonic components included in the voltage and
current of the main power supply (input) and the output (motor) side of the drive. Therefore, when measuring
with a meter for the commercial power frequency, use the meters shown in Table 8-3-1.
The power-factor cannot be measured using the power-factor meter available on the market which measures the
phase difference between voltage and current. When the power-factor must be measured, measure the power,
volt
age, and current on the input side and output side. Then, calc
ulate the power-factor using the following
formu
las:
Three-phase
Single -phase
Table 8-3-1 Meter for measuring the main circuit
(*1) When measuring the output voltage by rectifier type meter, an error may occur. Use a digital AC power meter
for good accuracy.
Power factor =
Electric power [W]
3
x Voltage [V] x Current [A]
x 100 [%]
Electric power [W]
Voltage [V] x Current [A]
x 100 [%]
Power factor =