Change during operation: N = impossible,
Y* = possible (enabled by using ), Y= possible (enabled by using
)
-46-
FUNC
DATA
F14 Restart mode after momentary power failure
This function determines whether operation is restarted upon recovery from momentary power failure:
0
Inactive
Failure while drive is stopped:
The stop status is continued after recovery from the failure.
Failure during operation:
LU indication is held immediately due to undervoltage and the drive
trips with alarm output.
1
Inactive
Failure while drive is stopped:
The stop status is continued after recovery from the failure.
Failure during operation:
LU indication is held upon recovery from the failure and the drive trips
with alarm output.
2
Active
The drive restarts with the frequency at the momentary power failure when 0.5s elapses after recov-
ery from the fail
3
Active
The drive restarts with the starting frequency when 0.5s elapses after recovery from the failure.
2
,
3
=
valid upon recovery from the failure with LU being on. The table below lists ap-
proximate LU indication times for a momentary power failure during operation.
Drive HP
1/8
1/4
1/2
1
2
3
5
[Second]
3 phase input
0.4
0.6
1.2
1.9
1.7
2.4
4.1
Single Phase Input
0.6
1.2
2.6
4.8
3.0
5.0
--
Frequency
limiter
(High)
Frequency
limiter
(Low)
This function sets the upper and lower limits of output frequencies.
0
to
1 2 0
If the upper limit and lower limit settings are reversed, the upper limit is
valid and the lower limit is ignored.
Hence, the operation is always performed with the upper limit regardless of the frequency setting.
Factory
setting
Change during
Operation
0
N
F14
0 to 120Hz can be set with a resolution of 1Hz.
F15
F16
Factory
setting
Change during
Operation
70Hz
Y
Factory
setting
Change during
Operation
0Hz
Y