-3-
Compliance with low voltage directive in EU [Continued]
!
CAUTION
Use of wires specified in Appendix C of EN 60204 is recommended.
Notes
1 The applicable frame and series of the molded case circuit breaker (MCCB) and ground fault
circuit breaker GFCB) will vary according to the short circuit capacity of the transformer sup-
plying the equipment. For selection details, refer to the relevant specifications.
2 The recommended wire size for the main circuit is referenced to the low voltage standards at
an ambient temperature of 40C.
3 The power supply impedance without a reactor is considered to be the equivalent of 0.1% of
drive capacity, with 10% current imbalance accompanied by voltage imbalance.
4 Crimp terminals up to 0.29” (7.4 mm) in width (including tolerance) can be used.
5 Crimp terminals up to 0.37” (9.5 mm) in width (including tolerance) can be used
6 Use a grounding cable of size equal to or larger than that of the input power supply cable.
7 Consult factory for availability.
** Indicates product revision
Recommended wire size AWG (mm
2
)
Molded case circuit
breaker (MCCB) or
ground fault circuit
breaker (GFCB)
Rated current [A]
Input circuit
2
3-phase 230V
[L1/R, L2/S, L3/T],
single phase 230V
[L1/L, L2/N]
Power
supply
volt-
age
Nominal
applied
motor
[HP]
Drive type
With
DCR
Without
Reactor
3
With
DCR
Without
Reactor
3
Output
circuit
2
[U. V. W]
DCR
2
circuit
[P1]
[P(+)]
Control
wiring
1/8
VM10E9ST32F12 **
1/4
VM10E9ST32F25 **
1/2
VM10E9ST32F50 **
5
1
VM10E9ST32001 **
5
10
2
VM10E9ST32002 **
15
3
VM10E9ST32003 **
10
20
14
(2.5)
4
14
(2.5)
4
14
(2.5)
4
14
(2.5)
4
3-phase 230V
5
VM10E9ST32005 **
20
30
12
(4.0)
5
10
(6.0)
5
12
(4.0)
5
12
(4.0)
5
1/8
VM10E9ST12F12 **
1/4
VM10E9ST12F25 **
5
1/2
VM10E9ST12F50 **
5
10
1
VM10E9ST12001 **
10
15
14
(2.5)
4
2
VM10E9ST12002 **
15
20
14
(2.5)
4
(4.0)
4
14
(2.5)
4
14
(2.5)
4
Single phase 230V
7
3
VM10E9ST12003 **
20
30
12
(4.0)
5
10
(6.0)
5
14
(2.5)
5
12
(4.0)
5
20
(0.5)