6 Configuration
61
For input 3 the EIS type „5“ is
set.
Here, the values of input 3 are
defined. The switch-off value
and the switch-on value have
the same function as with the
1-byte object (see p. 60). The
threshold values in this case
are defined by base and
factor. The actual value is re-
sulting from the product of
both parameters.
In the example given the
switch-on value is “5” (0.01 x
500=5) and the switch-off
value is “-1” (-0.01 x 100=-1).
Please observe with negative
values that the value will get
smaller if their absolute value
gets bigger (-10 is smaller
than -4).
6.3.4.5 Value Parameters for a 2-Byte Object
6.3.4 Function of the EIS Types
Содержание TC Plus analog
Страница 1: ...TC Plus Operating Instructions ...
Страница 23: ...5 Display Menu Guide 23 5 1 Initial Settings 5 Display Menu Guide ...
Страница 25: ...5 Display Menu Guide 25 5 1 Initial Settings 5 1 2 Provider for GSM Mode ...
Страница 26: ...5 1 Initial Settings 26 5 Display Menu Guide 5 1 3 Telephone Options for Analog Mode ...
Страница 27: ...5 Display Menu Guide 27 5 1 4 Telephone Options for ISDN Mode 5 1 Initial Settings ...
Страница 28: ...5 1 Initial Settings 28 5 Display Menu Guide 5 1 5 Options for GSM Mode ...
Страница 29: ...5 Display Menu Guide 29 5 1 6 Set Time Date 5 1 Initial Settings ...
Страница 30: ...30 5 Display Menu Guide 5 2 Edit Announcements 5 Display Menu Guide ...
Страница 31: ...5 Display Menu Guide 31 5 3 Configurate Alarm Inputs 5 Display Menu Guide ...
Страница 32: ...32 5 Display Menu Guide 5 4 Set Switching Outputs 5 Display Menu Guide ...
Страница 33: ...5 Display Menu Guide 33 5 5 Display Alarm Memories 5 Display Menu Guide ...
Страница 82: ...82 ...