34
May 2013
IMO_294_EN_v0
Roto E-Tec DoorDrive
Subject to change.
Optional settings
Authorisation period
5. Authorisation period
Authorisation means that the door receives a pulse, which indicates to the
door that the pulse transducers are authorised to operate the door.
The authorisation period enables the validity of an actuated authorisation to
be defined. If the authorised operation mechanism is used, the authorisa-
tion is then cancelled. In other words, the operation mechanism has to be
authorised again before each usage. The Roto setting for the authorisation
period is one minute.
Example:
DIP switch set to 01110111 (Roto setting): Following authorisa-
tion, the door has to be opened within a period of one minute. Operation
during authorisation does not extend the authorisation period, but rather it
cancels it. If the door is to then be closed again, authorisation has to be is-
sued once more to enable the door to be closed within the one minute pe-
riod.
DIP switch
Description
Feedback signal
Personal setting
0 1 1 1
0 0
0 0 Feedback on current setting
–
0 1
Authorisation for activation period
1
1 0 10 seconds
2
1 1 20 seconds
3
0 1
0 0 30 seconds
4
0 1 40 seconds
5
1 0 50 seconds
6
1 1 1 minute
7
1 0
0 0 1 minute 15 seconds
8
0 1 1 minute 30 seconds
9
1 0 1 minute 45 seconds
10
1 1 2 minutes
11
1 1
0 0 2 minutes 30 seconds
12
0 1 3 minutes
13
1 0 4 minutes
14
1 1 5 minutes
15