6 ROTEX control system ALPHA
+
23R
48
FA ROTEX ESU - 07/2008
Setting the maximum hot water temperature
• Set the maximum hot water temperature limit by changing parameter [4].
Setting the energy-saving hot water temperature
In order to minimise standby losses relating to the hot water storage tank, yet still maintain a comfortable minimum hot water
temperature, it is possible to set a temperature which the hot water storage tank must not fall below during economy mode
phases.
• Set the energy-saving hot water temperature by changing parameter [7].
6.6.8 Setting the maximum flow temperature
The flow temperature is the temperature the water is heated to before it is introduced into the heating circuit. Each heating circuit
has its own maximum flow temperature.
• Set the maximum flow temperature by changing the relevant parameter (see Table 6-9).
Direct heating circuit/Mixer circuit
Tab. 6-9
Dependencies between flow temperatures and the direct circuit
Hot water circuit
Tab. 6-10 Dependencies between flow temperatures and the hot water circuit
CAUTION:
If the Legionella protection function is activated, the hot water temperature may temporarily exceed 65 °C.
• If hot water is required during the disinfection phase, it must be mixed with cold water.
If the ST/OT contact is open, this temperature is maintained (only applies to automatic programmes 1 – 3 and
"reduced heating mode").
Parameter
Name
Maximum setting limit
Maximum flow temperature
95 °C
[12]*
Flow temperature, manufacturer
≤
Maximum flow temperature
[13]/[34]
Flow temperature, heating technician
≤
Maximum flow temperature, manufacturer
[28]/[35]
Flow heating curve at maximum temperature
≤
Maximum flow temperature, heating technician
(minimum 15 °C)
Note: Mixer temperatures are dealt with in the same way.
* Parameter can only be set by ROTEX.
Parameter
Name
Maximum setting limit
Maximum hot water temperature
95 °C
[12]*
Flow temperature, manufacturer
≤
Maximum flow temperature
[3]*
Hot water temperature, manufacturer
≤
Maximum flow temperature,
manufa 5 °C
[4]
Hot water temperature, heating technician
≤
Maximum hot water temperature, manufacturer
[5]
Hot water, user
≤
Maximum hot water temperature,
heating technician
[7]
Hot water temperature, energy-saving
≤
Maximum hot water temperature, user
[6]*
Absolute minimum hot water temperature
≤
Maximum hot water temperature,
energy-saving (minimum 2 °C)
* Parameter can only be set by ROTEX.