![Rotex E-Solar Unit ESU 509 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/rotex/e-solar-unit-esu-509/e-solar-unit-esu-509_installation-and-maintenance-instructions-manual_1491154041.webp)
6 ROTEX control system ALPHA
+
23R
41
FA ROTEX ESU - 07/2008
Overview of general system information
Info value no.
Info value
Can be viewed by
Comment
Installer
Operator
1
External temperature
x
x
If sensor value is available, otherwise "n. c." or "uuuu"
2
External working temperature
x
If no sensor value is available = 0 °C
3
ACTUAL flow temperature
x
x
4
TARGET flow temperature
x
5
Return flow temperature
x
x
6
Condition of the direct heating circuit
pump
x
0 = Off, 1 = On
7
TARGET mixer circuit temperature
x
8
ACTUAL mixer circuit temperature
x
x
9
Condition of the mixer circuit pump
x
0 = Off, 1 = On
10
Condition of the mixer motor
x
0 = Disconnected, 1 = Mixer open, –1 = Mixer closed
11
Flue gas temperature
x
If sensor value is available, otherwise "n. c." or "uuuu"
12
Hot water temperature
x
x
If sensor value is available, otherwise "n. c." or "uuuu"
13
Condition of the diverter valve
x
0 = Off, 1 = On
14
heat generator status
x
0 = no request from control
1 = request, but no BZ=0
2 = heat generator to (flame signal)
15
Hot water circuit clock timer
x
x
"AcT" = Active, "dEAC" = Inactive
16
Direct circuit clock timer
x
x
"AcT" = Active, "dEAC" = Inactive
17
Mixer circuit clock timer
x
x
"AcT" = Active, "dEAC" = Inactive
18
Condition of the modem contact
x
0 = Modem input
>
3.3 kOhms
±
200 ohms
The control is running in the operating mode that is currently set.
1 = Modem input = 3 kOhms
±
200 ohms
The control is running in continuous reduced mode for both circuits
(in acc. with parameter [11]).
2 = Modem input = 2.2 kOhms
±
200 ohms
The control is running in continuous reduced heating mode for both
circuits. The clock timer has no influence here.
3 = Modem input = 0 ohms or undefined
The control is running in standby mode for both circuits. Both
circuits are protected against frost.
19
Condition of the flow heater – lock
x
"STOP"; " "
20
Flow heater – starts
x
Number
21
Flow heater – elapsed hours
x
x
In hours
22
Total elapsed hours, heating system
x
x
In hours
Tab. 6-5
General info values (part I)
Содержание E-Solar Unit ESU 509
Страница 70: ...14 Notes 70 FA ROTEX ESU 07 2008...