Scenario 3: Master / Gearing mode to PT mode
The Kinetix 300 servo drive provides a Gearing mode that allows you to
connect a master TTL encoder signal for electronic gearing between that
master signal and this drive (slave).
The Kinetix 300 servo drive provides the Step and Direction mode and allows
you to connect a step and direction signal pair for position control.
shows the Properties window for Master To System Ratio in
MotionView for Kinetix 300 servo drives.
Figure 42 - Master To System Ratio in MotionView
The Kinetix 5100 drive uses PT mode for similar functionality.
The Kinetix 5100 servo drive can use a Master TTL signal from either the I/O
terminal block or the AUX (Auxiliary Feedback) connector. Consider that the
Master signal can be a standalone encoder or another Kinetix 5100 servo drive
using the buffered encoder outputs.
The E-Gear Ratio defines the gearing relationship. The Numerator and
Denominator are used to specify the ratio between Master and Slave counts.
The E-Gear parameters are shown in
. The Kinetix 5100 servo drive
provides four selectable gear ratios that can be switched by using digital
inputs.