Rockwell Automation Publication 2198-RM004C-EN-P - March 2022
17
Chapter 2 Replacement Considerations
Table 13 - Kinetix 5100 Input Power Specifications (single-phase and three-phase)
Attribute
2198-E1004-ERS
2198-E1007-ERS
2198-E1015-ERS
2198-E1020-ERS
AC input voltage
95…132V rms, single-phase (120V nom)
170…253V rms, single-phase (200…230V nom)
170…253V rms, three-phase (230V nom)
AC input frequency
47…63 Hz
Main AC input current
(1)
Nom (rms) 120V input (single-phase)
Inrush max (0-pk) 120V input
Nom (rms) 230V input (single-phase)
Inrush max (0-pk) 230V input
Nom (rms) 230V input (three-phase)
max Inrush max (0-pk) 230V input
4.08 A
0.84 A
4.79 A
1.40 A
2.84 A
1.44 A
7.88 A
0.76 A
8.85 A
1.32 A
5.20 A
1.40 A
12.22 A
0.76 A
14.41 A
1.36 A
7.87 A
1.44 A
18.40 A
2.56 A
21.36 A
4.40 A
11.57 A
4.64 A
Continuous output current (rms)
2.6 A
5.1 A
7.9 A
13.4 A
Continuous output current (0-pk)
3.7 A
7.2 A
11.2 A
18.9 A
Peak output current (rms)
(2)
6.5 A
15.4 A
23.7 A
40.6 A
Peak output current (0-pk)
9.2 A
21.8 A
33.5 A
57.4 A
Continuous power output
@ 120V nom
@ 230V nom
0.20 kW
0.40 kW
0.375 kW
0.75 kW
0.75 kW
1.50 kW
1.0 kW
2.0 kW
Internal shunt on
370V @120V AC input
370V @230V AC input
Internal shunt off
Internal shunt resistor
100 Ω
100 Ω
100 Ω
20 Ω
Internal shunt power
5 W
14 W
14 W
20 W
Undervoltage threshold
70V @120V AC input
150V @230V AC input
Overvoltage threshold
410V @120V AC input
410V @230V AC input
Bus capacitance
540 µF
1680 µF
1680 µF
2160 µF
Capacitive energy absorption
6.24 J
19.40 J
19.40 J
24.95 J
Short-circuit current rating
5,000 A (rms) symmetrical
(1)
Kinetix 5100 drive modules are limited to one AC mains power cycling per minute.
(2) Peak RMS current that is allowed for up to 1.8 seconds.
Table 14 - Kinetix 5100 Input Power Specifications (three-phase)
Attribute
2198-E2030-ERS
2198-E2055-ERS
2198-E2075-ERS
2198-E2150-ERS
AC input voltage
170…253V rms, three-phase (230V nom)
AC input frequency
47…63 Hz
Main AC input current
(1)
Nom (rms) 230V input (three-phase)
Inrush max (0-pk) 230V input
14.65 A
4.42 A
27.32 A
9.55 A
37.90 A
28.68 A
70.45 A
32.0 A
Continuous output current (rms)
17.9 A
41.3 A
49.0 A
78.0 A
Continuous output current (0-pk)
25.3 A
58.4 A
69.3 A
110.3 A
Peak output current (rms)
(2)
55.95 A
91.4 A
127.5 A
162.0 A
Peak output current (0-pk)
79.1 A
129.2 A
180.3 A
229.1 A
Continuous power output
@ 230V nom
3.0 kW
5.5 kW
7.5 kW
15.0 kW
Internal shunt on
370V @230V AC input
Internal shunt off
Internal shunt resistor
20 Ω
—
—
—
Internal shunt power
20 W
—
—
—
Undervoltage threshold
150V @230V AC input
Overvoltage threshold
410V @230V AC input
Bus capacitance
2160 µF
4100 µF
7000 µF
13,500 µF
Capacitive energy absorption
24.95 J
47.36 J
69.30 J
155.93 J
Short-circuit current rating
5,000 A (rms) symmetrical
(1)
Kinetix 5100 drive modules are limited to one AC mains power cycling per minute.
(2) Peak RMS current that is allowed for up to 1.8 seconds.