Rockwell Automation Publication 2198-RM004C-EN-P - March 2022
21
Chapter 2 Replacement Considerations
You can assign the inputs that are listed as — for any of these functions.
•
Abort Homing
•
Abort Index
•
Start Homing
•
Start Index
•
Fault Reset
•
Home Sensor
•
Index Select
The digital inputs are optically isolated and sink up to 24V DC. Electrical
details are shown in
.
Kinetix 5100 Drives
The Kinetix 5100 drives have eight standard inputs and two-high speed inputs,
both with configurable functions. The digital inputs on Kinetix 5100 drives
have the same physical characteristics.
shows the Kinetix 5100 digital
inputs physical characteristics.
Table 20 - Kinetix 300 Drives Fixed Digital Input Assignments
Digital Input
Function
IN_A1 (pin 27)
Negative travel limit input
IN_A2 (pin 28)
Positive travel limit input
IN_A3 (pin 29)
Inhibit/enable input
IN_A4 (pin 30)
—
IN_B1 (pin 32)
—
IN_B2 (pin 33)
—
IN_B3 (pin 34)
—
IN_B4 (pin 35)
—
IN_C1 (pin 37)
—
IN_C2 (pin 38)
—
IN_C3 (pin 39)
Registration sensor input
IN_C4 (pin 40)
—
Table 21 - Kinetix 300 Digital Input Signal Specifications
Attribute
Value
Scan time
500 µs
Current max
9 mA, typical
Input impedance
1.2 k
Ω
, typical
Voltage range
5…24V DC
Table 22 - Kinetix 5100 Digital Input Signal Specifications
Attribute
Value
Digital Input response (delay)
Standard inputs: 1.25 ms max
High-speed inputs: 3 µs
Digital Input scan time
Standard inputs: 500us max
High-speed inputs: 1µs
ON state voltage
15V min, 26.4V max
ON state Current
2.0 mA min, 6.0 mA max
OFF state voltage
-1.0 V min, 5V max