GAHP-AR – Installation, start-up, use and maintenance manual
92
Edition:
2014-08
E 604
INADEQUATE VENTILATION / CONDENSER OVERHEATING
CODE GENERATED BY
:
U
604 code generated 2 times in 2 hours of operation.
RESET METHOD
:
Carry out appropriate checks. Reset may be performed through the S61 board via menu 2, Parameter 1.
If the code persists, contact Robur TAC.
E 605
HIGH AMBIENT TEMPERATURE
CODE GENERATED BY
:
HIGH temperature detected by ambient temperature sensor.
RESET METHOD
:
Reset occurs automatically when the condition that generated the code ceases, with hysteresis of 3.6 °F.
E 606
LOW AMBIENT TEMPERATURE
CODE GENERATED BY
:
LOW temperature detected by ambient temperature sensor.
RESET METHOD
:
Reset occurs automatically when the condition that generated the code ceases, with hysteresis of 3.6 °F.
U
607
HIGH CONDENSER INLET TEMPERATURE
CODE GENERATED BY
:
High temperature detected by condenser inlet temperature sensor (T> limit set: menu 1, Parameter 66).
RESET METHOD
:
Reset occurs automatically when the condition that generated the code ceases, with hysteresis of 90 °F.
E 607
HIGH CONDENSER INLET TEMPERATURE
CODE GENERATED BY
:
U
607 code active for 1 hour, or
U
607 code generated 12 times in 2 hours of operation.
RESET METHOD
:
Carry out appropriate checks. Reset may be performed via S61 board, menu 2, Parameter 1 (or via
DDC). If the code persists, contact Robur TAC.
E 608
FLAME CONTROL UNIT ERROR
CONDIZIONI DI INTERVENTO
: E612 code on GAHP-AR in and inlet temperature increasing by over 18 °F within 1 hour.
RESET METHOD
:
Carry out appropriate checks. Reset may be performed via S61 board, menu 2, Parameter 1 (or via
DDC). If the code persists, contact Robur TAC.
U
610
WATER CIRCUIT FLOWMETER:
Insufficient water flow
CODE GENERATED BY
:
Insufficient water flow (the circulator is "on" and the water flowmeter remains "open").
RESET METHOD
:
Reset occurs automatically when correct water flow is restored or if the circulation pump goes off.
E 610
WATER CIRCUIT FLOWMETER:
Insufficient water flow
CODE GENERATED BY
:
U
610
code generated 5 times since appliance was powered, or code
U
610 is active for 1 hour.
RESET METHOD
:
Reset may be performed via S61 board, menu 2, parameter 1 (or via DDC). If the Code persists, contact
Robur TAC.
U
611
INSUFFICIENT ROTATION OF OIL PRESSURE PUMP
CODE GENERATED BY
:
Insufficient rotation of oil pressure pump.
RESET METHOD
:
Reset occurs automatically 20 minutes after the code is generated.
E 611
INSUFFICIENT ROTATION OF OIL PRESSURE PUMP
CODE GENERATED BY
:
U
611
code generated 2 times in 2 hours of operation.
RESET METHOD
:
Reset may be performed via S61 board, menu 2, Parameter 1 (or via DDC). If the code persists, contact
Robur TAC.
U
612
FLAME CONTROL UNIT ARREST
CODE GENERATED BY
:
Burner ignition failure.
RESET METHOD
:
Reset occurs automatically when the solenoid valve opens again (new ignition attempt).
Содержание GAHP Line AR Series
Страница 6: ...GAHP AR Installation start up use and maintenance manual 2 Edition 2014 08 ...
Страница 30: ...GAHP AR Installation start up use and maintenance manual 26 Edition 2014 08 ...
Страница 52: ...GAHP AR Installation start up use and maintenance manual 48 Edition 2014 08 ...
Страница 61: ...Electrical installer section Ed 2014 08 57 Figure 22 Internal electrical wiring diagram ...
Страница 82: ...GAHP AR Installation start up use and maintenance manual 78 Edition 2014 08 ...