Overview and technical specifications section
Ed.
2014-08
11
HEATING MODE CAPACITY – Btu/hr
OUTLET (TO PLANT) HOT WATER TEMPERATURE
EXTERNAL
AMBIENT
OPERATING
TEMPERATURE
(DRY BULB)
86°F 113°F 122°F
140°F
∆
T=18°F
∆
T=27°F
-20.0°F
91.1 82.9 82.9
80.9
-13.0°F
92.1 83.9 83.9
81.9
-4.0°F
93.2 85.0 85.0
82.9
5.0°F
97.2 89.4 88.0
85.6
14.0°F
105.4 94.5 92.1
90.1
19.4°F
111.9 100.3 96.9 95.5
35.6°F
123.9 118.7 109.9
102.4
44.6°F
129.3 128.0
1
1
2
2
0
0
.
.
4
4
112.6
50.0°F
131.7 131.0 124.2
117.7
59.0°F
134.1 133.4 128.3
122.2
68.0°F
134.8 134.4 129.3
123.9
77.0°F
134.8 134.4 129.7
126.2
Table 5 -
Heating mode capacity. Nominal value is in bold type.
CHILLING MODE CAPACITY - Btu/hr
OUTLET (TO PLANT) CHILLED WATER TEMPERATURE
37.4°F 44.6°F 50.0°F
EXTERNAL
AMBIENT
OPERATING
TEMPERATURE
(DRY BULB)
∆
T=9°F
59.0°F
64.8 63.8 64.3
68.0°F
63.5 63.5 64.1
77.0°F
60.1 62.4 63.3
86.0°F
54.3 60.7 61.8
95.0°F
44.0
5
5
7
7
.
.
7
7
59.4
104.0°F
51.2
54.6
113.0°F
46.1
Table 6
-
Chilling mode capacity. Nominal value is in bold type.
Содержание GAHP Line AR Series
Страница 6: ...GAHP AR Installation start up use and maintenance manual 2 Edition 2014 08 ...
Страница 30: ...GAHP AR Installation start up use and maintenance manual 26 Edition 2014 08 ...
Страница 52: ...GAHP AR Installation start up use and maintenance manual 48 Edition 2014 08 ...
Страница 61: ...Electrical installer section Ed 2014 08 57 Figure 22 Internal electrical wiring diagram ...
Страница 82: ...GAHP AR Installation start up use and maintenance manual 78 Edition 2014 08 ...