BURNER SPECIFICATIONS
GAS INPUT (HHV)
kBtu/hr
95.5
ELECTRICAL RATINGS
REQUIRED VOLTAGE, 60 HZ, SINGLE PHASE
(2)
V
208 - 230
MINIMUM CIRCUIT AMPACITY (MCA) Unit only
A
8.0
MAXIMUM OVER CURRENT PROTECTION (MOCP)
A
10.9
TOTAL ELECTRICAL OPERATING CONSUMPTION (NOMINAL)
(3)
kW
0.75
PHYSICAL DATA
SHIPPING WEIGHT
Pounds
883
OPERATING WEIGHT
Pounds
838
UNIT WATER VOLUME
(4)
Gallons
0.79
DIMENSIONS
(5)
WIDTH
LENGTH
HEIGHT
Inches
33
1
/
2
48
1
/
2
57
WATER CONNECTIONS (INLET / OUTLET)
FPT
1” 1/4
GAS INLET CONNECTION
FPT
1
/
2
HEATER GASES DUCT INTERNAL DIAMETER
Inches
3
1
/
8
Table 4
-
GAHP-AR technical data
(2) UNITS ARE FACTORY-WIRED FOR 208-230 VOLTS OPERATION.
(3) MAY VARY BY ±10% AS A FUNCTION OF BOTH POWER SUPPLY AND ELECTRICAL MOTOR INPUT TOLERANCE.
(4) REFERRED TO A SOLUTION OF QUALITY TAP WATER AND 10% BY VOLUME OF INHIBITED PERMANENT ANTIFREEZE. HIGHER
ANTIFREEZE CONCENTRATIONS MAY BE REQUIRED IN CERTAIN APPLICATIONS. MONO-ETHYLENE GLYCOL CAUSES
CORROSION PHENOMENON IN GALVANIZED METAL PIPES.
(5) FOR GASES DUCT DIMENSIONS SEE FIGURE 3, PAGE 14.
Содержание GAHP Line AR Series
Страница 6: ...GAHP AR Installation start up use and maintenance manual 2 Edition 2014 08 ...
Страница 30: ...GAHP AR Installation start up use and maintenance manual 26 Edition 2014 08 ...
Страница 52: ...GAHP AR Installation start up use and maintenance manual 48 Edition 2014 08 ...
Страница 61: ...Electrical installer section Ed 2014 08 57 Figure 22 Internal electrical wiring diagram ...
Страница 82: ...GAHP AR Installation start up use and maintenance manual 78 Edition 2014 08 ...