GAHP-AR – Installation, start-up, use and maintenance manual
32
Edition:
2014-08
Figure 9 -
Clearances from vent outlets, chimney flues and air intake openings.
Place the appliance, preferably, in a position that is not in the immediate vicinity of rooms
and/or spaces where a high degree of quiet is required, such as bedrooms, meeting
rooms, etc.
Evaluate the acoustic impact of the appliance on the basis of the installation site: avoid
locating the appliance in positions (corners of buildings, etc.) that could amplify the noise it
produces (reverb effect). See the following figure:
Figure 10 –
Location of the unit.
3.3 HYDRAULIC CONNECTIONS
General indications
•
The hydraulic plant may be created using pipes in stainless steel, black steel, copper
or cross linked polyethylene for heating/cooling plants. All water pipes and pipe
connections must be adequately insulated in accordance with current regulations, to
prevent heat loss and the formation of condensate.
•
If glycol antifreeze is to be used (see Paragraph 3.5 on page 39), DO NOT USE
galvanized pipes, as they are potentially subject to corrosion phenomena in the
presence of glycol.
BEDROOMS
LIVING
ROOM
GA
RA
GE
GOOD
BETTER
IDEAL
AVOID
INSTALLATION IN
THIS AREA
ROOF / TERRACE INSTALLATION
GROUND INSTALLATION
6 FT. MIN
6 FT. MI
N.
8 FT. MIN.
8 FT. MIN.
Содержание GAHP Line AR Series
Страница 6: ...GAHP AR Installation start up use and maintenance manual 2 Edition 2014 08 ...
Страница 30: ...GAHP AR Installation start up use and maintenance manual 26 Edition 2014 08 ...
Страница 52: ...GAHP AR Installation start up use and maintenance manual 48 Edition 2014 08 ...
Страница 61: ...Electrical installer section Ed 2014 08 57 Figure 22 Internal electrical wiring diagram ...
Страница 82: ...GAHP AR Installation start up use and maintenance manual 78 Edition 2014 08 ...