GAHP-AR – Installation, start-up, use and maintenance manual
96
Edition:
2014-08
E 684
FAULTY CONNECTION TRANSFORMER OR 24 Vac FUSES
CODE GENERATED BY
:
Damage to one of the 2 24-0-24 Vac transformer fuses, or one of 24-0-24 Vac wires to the board not
supplying current.
RESET METHOD
:
Check fuses and 24-0-24 Vac electrical power connections on the board. Reset may be carried out via
the S61 board, Parameter 1 (or via DDC). If the code persists or occurs again, contact Robur TAC.
E 685
INCORRECT MODULE TYPES (from menu 6)
CODE GENERATED BY
:
The module type set (from menu 6) does not correspond to the one managed by the board.
RESET METHOD
:
Reset occurs automatically when the correct parameters are entered.
If the code persists, contact Robur TAC.
E 686 - and 687 - and 688 - and 689
MEMORY TEST UNSUCCESSFUL
CODE GENERATED BY
: Processor
error.
RESET METHOD
:
Contact Robur TAC.
E 690
AMBIENT TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY
:
Interruption or short circuit of ambient temperature sensor.
RESET METHOD
:
Reset may be performed via S61 board, menu 2, Parameter 1 (or via DDC). If the code persists, contact
Robur TAC.
E 691
BOARD DEFECTIVE
CODE GENERATED WHEN
:
One of the following is absent: serial number of board, hardware version code or encryption key written
during board test.
RESET METHOD
: Contact
ROBUR
TAC.
Table 27 -
Operating codes generated by the electronic control board S61 (firmware release 3.0
27
).
In the table,
TAC
= Robur authorized Technical Assistance Centre.
The following figure shows a reference scheme of the unit ignition system.
Figure 39 -
Ignition transformer, igniter assembly and flame sensor.
LEFT SIDE OF
COMBUSTION CHAMBER
1
2
3
4
6
1
2
3
4
5
5
6
IGNITION TRANSFORMER
IGNITION CABLES
FLAME SENSOR
ANTI-SPARK INSULATORS
IGNITER
IGNITER GASKET
NOTE: SOME DETAIL
HAS BEEN REMOVED
FOR CLARITY
Содержание GAHP Line AR Series
Страница 6: ...GAHP AR Installation start up use and maintenance manual 2 Edition 2014 08 ...
Страница 30: ...GAHP AR Installation start up use and maintenance manual 26 Edition 2014 08 ...
Страница 52: ...GAHP AR Installation start up use and maintenance manual 48 Edition 2014 08 ...
Страница 61: ...Electrical installer section Ed 2014 08 57 Figure 22 Internal electrical wiring diagram ...
Страница 82: ...GAHP AR Installation start up use and maintenance manual 78 Edition 2014 08 ...