Measuring Current
If the value measured is 0 mA, then: the loop wires are broken, the sensor assembly is not
powered up, the sensor assembly is malfunctioning, or the controller is malfunctioning. A
digital multi-meter (DMM), or current meter, may be used in conjunction with the controller
and/or to test the 4-20 mA current loop signal. To measure the current, place the meter probes
in line with the current loop.
Sensor Element Scale Ranges
Sensor Type
Gas Type
Formula Range
Photo Ionization
Detector (PID)
Volatile Organic Compounds VOC10
0-10 PPM
Photo Ionization
Detector (PID)
Volatile Organic Compounds VOC20
0-20 PPM
Photo Ionization
Detector (PID)
Volatile Organic Compounds VOC50
0-50 PPM
Photo Ionization
Detector (PID)
Volatile Organic Compounds VOC1K
0-1000 PPM
Photo Ionization
Detector (PID)
Volatile Organic Compounds VOC2K
0-2000 PPM