VOC Pro Transmitter • 33
If the fault terminal cannot be used, RKI Instruments recommends one of the following
configurations:
Relay 1: Fail-Safe Setting
1. If necessary, enter the Product Settings and Configuration menu by pressing and holding
the MENU button for 6 seconds.
2. Press and release the MENU button until the Relay 1 Failsafe screen appears.
3. Use the ADD and SUB buttons to select the desired fail-safe setting for Relay 1. Select
“Yes” to turn the fail-safe setting on, or select “No” to leave the fail-safe setting off.
4. Press the MENU button to select the desired setting and to advance to the Relay 2 fail-safe
setting screen.
Relay 2: Fail-Safe Setting
1. If necessary, enter the Product Settings and Configuration menu by pressing and holding
the MENU button for 6 seconds.
2. Press and release the MENU button until the Relay 2 Failsafe screen appears.
3. Use the ADD and SUB buttons to select the desired fail-safe setting for Relay 2. Select
“Yes” to turn the fail-safe setting on, or select “No” to leave the fail-safe setting off.
4. Press and release the MENU button to move through the Product Settings and
Configuration menu or to exit to the normal operating mode screen.
Recommended Configurations for Relay Fail-Safe Setting
Power Source
Relay Wiring
Fail-Safe
Outcome
VOC Pro
Normally-Closed (NC)
No (Off)
Normal Operation: Closed
Alarm Activation: Open
VOC Pro
Normally-Open (NO)
Yes (On)
Normal Operation: Closed
Alarm Activation: Open
External Power Supply
Normally-Closed (NC)
Yes (On)
Normal Operation: Open
Alarm Activation: Closed
External Power Supply
Normally-Open (NO)
Yes (On)
Normal Operation: Closed
Alarm Activation: Closed