7-1
IMSBR10-E1
Setup Operations for Changing/Adding Functions (Basic Setting Mode)
7
7.1 Changing the Auxiliary Alarm Function
This section explains the details of setting the alarm system items listed below.
• Diagnosis output using the alarm output relay (I01)
• Reflash alarm operation of the alarm output relay (I01 to I03)
• AND/OR operation of alarm output relays
• Energized/De-energized operation of alarm output relays when alarms occur
• Hold/Non-hold operation of alarm output relays
• Hold/Non-hold operation of alarm indications
• The interval of the rate-of-change alarm
• Alarm hysteresis
Basic Setting mode cannot be entered when recording is in progress or when computation is in progress on
models with the computation function (/M1 option).
Procedure
Changing the Settings
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the
and
keys simultaneously for 3 seconds to enter Basic Setting mode.
3.
Press the
key with Alarm shown on the screen.
4.
Set each item and press the
key.
Use the
key or
SHIFT
+
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC
key in the middle of the operation, the settings entered up to then are cancelled,
and the display returns to a higher level menu.
5.
When the
Setting complete
screen appears, do either of the following:
To correct the setting, press the
key.
If you are done, press the
ESC
key.
Chapter 7 Setup Operations for Changing/Adding Functions (Basic Setting Mode)
Содержание SBR-EW180
Страница 1: ...IMSBR10 E1 SBR EW180 Recorder User s Manual...
Страница 2: ......
Страница 14: ......
Страница 233: ...3 2002...