2-5
IMSBR10-E1
Before Using the Recorder
2
2.3 Input Signal Wiring
General Precautions to Be Taken While Wiring
WARNING
To prevent the possibility of electric shock when wiring, make sure that the power supply source is
turned OFF.
CAUTION
• If a strong tension is applied to the cable wired to the recorder, the terminals of the recorder and/or the
cable can be damaged. In order to prevent tension from being applied directly on the terminals, fasten
all wiring cables to the rear of the mounting panel.
• Do not apply a voltage exceeding the following value to the input terminals as this may damage the
recorder.
• Maximum input voltage
Voltage range less than or equal to 200 mVDC, TC, RTD, and DI:
±
10 VDC
Ranges other than those listed above:
±
60 VDC
• Maximum common-mode voltage
±
60 VDC (under measurement category II conditions)
• The recorder is an INSTALLATION CATEGORY II product.
Precautions to Be Taken While Wiring
Take the following precautions when wring the input signal cables.
It is recommended that crimp-on lug with insulation sleeves (designed for
4-mm screws) be used when connecting the input/output signal wires to
the terminals. However, this does not apply clamped terminals (/H2).
Crimp-on lug with insulation
sleeves (for 4 mm screws)
For clamped terminals (/H2), the following wire is recommended.
• Conductive cross-sectional area for single wire: 0.14 mm
2
to 1.5 mm
2
, stranded wire: 0.14 mm
2
to 1.0 mm
2
• Length of the stripped section of the wire: Approx. 5 mm
Take measures to prevent noise from entering the measurement circuit.
• Move the measurement circuit away from the power cable (power circuit) and ground circuit.
• It is desirable that the object being measured does not generate noise. However, if this is unavoidable, isolate
the measurement circuit from the object. Also, ground the object being measured.
• Shielded wires should be used to minimize noise caused by electrostatic induction. Connect the shield to the
ground terminal of the recorder as necessary (make sure you are not grounding at two points).
• To minimize noise caused by electromagnetic induction, twist the measurement circuit wires at short, equal
intervals.
• Make sure to earth ground the protective ground terminal through minimum resistance (less than 100
Ω
).