4. MODBUS COMMUNICATION PROTOCOL
IMR02F04-E1
37
4.6.4 Preset multiple registers [10H]
The query message specifies the starting register address and quantity of registers to be written.
The write data is arranged in the query message with high-order 8-bit first and low-order 8-bit next. Only
R/W holding registers can be specified.
Example: Data is written into the two holding registers from 00F4H [Alarm 1 set value] to 00F5H
[Alarm 2 set value] of slave address 1.
Query message
Slave address
01H
Function code
10H
Starting number
High
00H
Low
F4H
Quantity
High
00H
Low
02H
Number of data
04H
Data to first register
High
00H
(Low-order word)
Low
32H
Data to next register
High
00H
(High-order word)
Low
32H
CRC-16 High
DDH
Low
02H
Normal response message
Slave address
01H
Function code
10H
Starting number
High
00H
Low
F4H
Quantity
High
00H
Low
02H
CRC-16 High
00H
Low
3AH
Error response message
Slave address
01H
80H
Function code
90H
Error code
02H
CRC-16 High
CDH
Low
C1H
First holding register address
The setting must be between 1 (0001H) and
123 (007BH).
Number of holding registers
2
Any pertinent data