4. MODBUS COMMUNICATION PROTOCOL
IMR02F04-E1
29
4.2 Function Code
Function code contents
Function code
(Hexadecimal)
Function
Contents
03H Read
holding
registers Measured
value (PV), Alarm status monitor,
etc.
06H
Preset single register
Alarm set value, PV bias, etc.
08H
Diagnostics (loopback test)
Loopback test
10H
Preset multiple registers
Alarm set value, PV bias, etc.
Message length of each function (Unit: byte)
Function code
Function
Query message
Response message
(Hexadecimal)
Min
Max
Min
Max
03H Read
holding
registers 8 8 7 255
06H
Preset single register
8
8
8
8
08H Diagnostics
(loopback
test)
8 8 8 8
10H Preset
multiple
registers 11
255 8 8
4.3 Communication Mode
Signal transmission between the master and slaves is conducted in Remote Terminal Unit (RTU) mode.
Items
Contents
Data bit length
8-bit (Binary)
Start mark of message
Unused
End mark of message
Unused
Message length
Refer to
4.2 Function code
Data time interval
Less than 24-bit time *
Error check
CRC-16 (Cyclic Redundancy Check)
* When sending a command message from the master, set intervals of data configuring one message to
time shorter than the 24-bit time. If time intervals become time longer than the 24-bit time the relevant
slave assumes that message sending from the master is terminated and there is no response.