Checking the availability of the material
60 days prior to the date determined for interventions of maintenance, perform a detailed examination of the
material necessary:
1.
check if the material is on the stock,
2.
if necessary, ask the manufacturer's Technical Office for the missing parts at least 30 days in advance.
5.1.
Maintenance and cleaning
DANGER: the Manufacturer cannot be held in any way liable for any damage caused to property or
persons due to incorrect or incomplete maintenance.
DANGER: before carrying out any scheduled ordinary maintenance, ensure the partly-completed
machine has been disconnected from the mains; wait for the hot surfaces to cool.
ATTENTION: in the event the machine parts require replacement, only use original spare parts.
ATTENTION: any brazing operations in the products must be carried out by qualified personnel.
5.1.1.
Interventions and relative periodicity
ATTENTION: At the end of maintenance, replace all previously removed guards.
DESCRIPTION OF THE MAINTENANCE
FREQUENCY
Electrical terminals connection check
Check the tightness of all the electrical terminals both inside the electrical panels and in
the terminals of each electrical utility.
Monthly
Check for refrigerant and oil leaks
Visually check the entire refrigerant circuit for refrigerant leaks, including inside the partly-
completed machine. These leaks are also evident from traces of lubricating oil. Intervene
promptly and investigate further in case of uncertainty.
Monthly
Check efficiency of the earthing
Check the earthing terminal and its efficiency with appropriate instrumentation.
Monthly
Cleaning of gascooler and intercooler (if present)
Periodically clean the gascooler and intercooler (if present) removing dust and grease.
The surface of the finned pack must be perfectly free, the air flow must not be obstructed
by dust or by other deposited material.
For cleaning use a compressed air gun or, alternatively, an aspirator.
Monthly
Clean the air filters
Check and if necessary clean the air filters (if present).
During certain periods, especially in spring, it is necessary to perform the cleaning
operation earlier due to the presence of increased impurities in the air.
Monthly
Check electrical cables status
Check that the cables inside the machine compartment do not show any alterations of
any kind (abrasion, burns, deterioration, etc.) Any possible variation in cable quality
requires immediate replacement of the same.
Monthly
Check the tightness of the cable glands.