Looking at the display on the door of the partly-completed machine electrical panel the following are evident:
BUTTONS
ASSOCIATED
ALARM
It shows the list of active alarms and access to the alarm logs
PRG.
It is used to enter the main menu
BACK
Return to the previous page
UP
To switch to the upper value in a list or to increase the value of a variable
highlighted by the cursor.
DOWN
To switch to the lower value in a list or to decrease the value of a variable
highlighted by the cursor.
ENTER
Enter the selected sub-menus or confirm the set values
MANAGEMENT OF LED SIGNALS
BUTTONS
ASSOCIATED
Red
Flashing: Active alarms not seen
Fixed: Alarms seen
Yellow
Control Hecu CO2 in state of ON
Green
Control Hecu CO2 powered
x
Bring the application software that manages the compressors to ON;
Inside the electrical panel there are two electronic boards: one for the management of the high pressure part
of the partly-completed machine (heat recovery, gas-cooler, back pressure valve, gas flash valve, etc.) and
one for the management of BLDC rotary compressors.
Normally, the display on the electrical panel is connected (via a 6-pole telephone cable) to the
management controller of the high-pressure part (pRack application). Therefore to turn the software of the
second controller ON, it is necessary to disconnect the telephone cable connected to the display and to
attach the second telephone cable located nearby. In this way accessibility is provided to the second
controller.
x
Turn the pRack CO2 application ON;
The steps to be taken on the second application are the following: